Cand. tech. sci Kostinsky S.S.

Platov South-Russian State Polytechnic University (Novocherkassky polytechnic institute), the Russian Federation

 

Loss evaluation of the active electric power in tank and air transformers at the uniform and non-uniform load pattern

 

The electrical energy lost in the transformer in the course of transformation alternating-current, is oozed in the form of heat in windings, magnetic system and other parts of the transformer. In tank transformers magnetic system and windings are washed by the circuit-breaker oil, which level considerably above level of magnetic system. The particles of oil adjoining to hot surfaces, heating up, direct upwards and donate heat in a environment through walls and a cap of a tank. Between windings both magnetic system, on the one hand, and oil - with another, the certain temperature difference is erected. However the temperature of oil and other parts of the transformer in different zones on height are various.

In view of complexity of thermal processes in the transformer at their theoretical analysis it is necessary to do a series of simplifications. With that end in view windings and the magnetic system, representing a combination of various materials, exchange the homogeneous skew fields. Such simplification is admissible provided that the substituting homogeneous skew field at the same external sizes and the same amount of oozed heat possesses the equivalent heat capacity. Besides, for each device thermal chains (the magnetic system, a winding, oil, a tank) introduce some its medial temperature.

According to [1] oozed in a skew field for the elemental time interval dt thermal energy Ï · dt partially is spent for skew field rise in temperature on and partially tapped in environmental space. At any moment the balance of thermal energy expressed by a differential equation takes place

Ï · dt = Ñ ·  + K · υ · dt,

where Ñ – the full heat capacity of a skew field;

K – amount of heat tapped by a heat-absorbent surface in unit of time at a difference between temperature of a surface and temperature of medium in 1°Ñ;

υ – temperature difference between the given skew field and a surrounding medium.

The heating of the transformer concerning oil at the erected thermal conditions can be accepted to proportional losses in the transformer.

Deficiency of the definition of losses of the active electrical energy featured above an expedient of the transformer is that for account meanings of the physical quantities depending on design data of the transformer are required, not being nameplate data and complicated for definition in practice with a split-hair accuracy.

Counters of losses of the active electric power are applied to definition of losses for example [2] which principle of operation is grounded on Joule law. Deficiency of such counters is that they spot energy of losses in transformer windings, but losses also include losses in magnetic system, a tank, and as losses from asymmetry and a nonsinusoidal current. For the account of losses also it is necessary to know resistance of object on which measuring which varies depending on heating and surrounding medium temperature are made. Told all above leads to a drop of a measurement accuracy of losses of electrical energy.

On the basis of law of conservation energy it is possible to note heat-balance equation in other form:

                                (1)

where ΔP – active power losses in the transformer for dt;

ñ – specific heat capacity;

G – transformer weight;

dΘ – increase of temperature of the transformer;

α – coefficient of a heat dissipation from a surface;

S – surface area;

ΔΘ – difference between temperature of the transformer and an environment temperature.

The transformer heating time constant is spotted according to [1]:

.                                                  (2)

At reaching of the erected temperature the first addend in the formula (1) becomes equal to zero, and losses become equal to losses in the nominal condition and develop of idling and short circuit losses.

According to the formula (2) at the erected temperature of the transformer taking into account that in the nominal mode of operation of the transformer ΔР= Ðind + Ðs.c., the equation (1) will become:

,

whence 

,                                      (3)

where Ðind – idling losses;

Ðs.c. – short circuit losses;

Θn – the erected temperature of the transformer in the nominal condition.

Using the equations (2) and (3) it is discovered α · S:

.                                 (4)

Considering, that G, c, S and α are constants for the concrete transformer and, using formulas (3) and (4), the law of conservation energy (1) will become:

.       (5)

Composed formulas (5) have the following physical sense:

 – stored heat amount in the transformer;

 – amount of heat donated in a surrounding medium.

Losses of active electrical energy in magnetic system and transformer windings are oozed in the form of heat. As it was specified in the beginning of paper in view of complexity of thermal processes in the transformer at their theoretical analysis it is necessary a winding and the magnetic system, representing a combination of various materials, to exchange the homogeneous skew fields. The specified assumption leads to increase of an error of evaluation of heat oozed with devices of a construction of the transformer since the magnetic system at a normal mode of operation heats up essentially less, than a winding drawings 1 and 2. Installation sites of the temperature sensing devices which effects of measuring are shown in drawings 1, 2, are given in drawing 3.

Fig. 1. The graph of a modification of temperature of a winding from time: 1, 2 – the approximated data gained from temperature sensing devices 5 and 6 (fig. 3) accordingly; 3 – medial meaning of temperature

Fig. 2. The graph of a modification of temperature of magnetic system from time: 1 – 4 – the approximated data gained from temperature sensing devices 1 – 4 (fig. 3); 5 – medial meaning of temperature

 

For the purpose of reduction of an error of account of losses of the active electric power for the air transformer it is necessary to part the losses oozed in magnetic system and a winding and then expression (5) will become:

,            (6)

where Òind – heating time constant of magnetic system;

ΔΘind – difference between temperature of magnetic system and a surrounding medium;

dΘind – gain of temperature of magnetic system for space of time dt;

Òs.c. – heating time constant of winding;

ΔΘs.c. – difference between temperature of winding and a surrounding medium;

dΘs.c. – gain of temperature of a winding for space of time dt;

Θn ind – the erected temperature of magnetic system in the nominal condition;

Θn s.c. – the erected temperature of a winding in the nominal condition.

Fig. 3. Installation sites of temperature sensing devices on the single-phase air transformer: 1 – 4 – temperature sensing devices anchored on magnetic system of the transformer; 5, 6 – temperature sensing devices anchored on a transformer winding; 7 – a temperature sensing device for environment temperature measuring; 8 – magnetic system; 9 – a winding; 10 – transformer bases

 

Composed formulas (6) have the same physical sense, as composed formulas (5).

For the purpose of checkout of working capacity of expression (6) experiment on the single-phase air transformer with use of the measuring probing devices which have transited metrological checking has been made. Transformer temperature sensing devices have been anchored on magnetic system and a winding, the data unit for measuring of an environment temperature near to the transformer also has been provided. Installation sites of temperature sensing devices corresponded to places shown on drawing 3.

Fig. 4. The graph of an error of evaluation of losses of the active electric power in the transformer from time: 1 – the calculated meanings; 2 - approximation of the calculated meanings by a multinomial of 4-th order

 

The graph of an error of evaluation of losses of the active electric power in the transformer under the formula (6) in comparison with the real (measured) losses is given in drawing 4. Medial meaning of quantity of an error of evaluation of losses of the active electric power in the transformer during measuring has made 9,2 %.

The formula (6) is valid, as it was specified above, for the nominal condition of the transformer as idling and short circuit losses are accepted by the invariable. Actually at real loadings the transformer fill varies, owing to what quantity of losses varies. In this connection at definition of losses of the electric power it is necessary to discover a power loss in the transformer on each i-th time interval dt. The solution of a differential equation (1) for such intervals looks like:

,                     (7)

where Θi – temperature of a separate device of the transformer;

Θi+1 – temperature of a separate device of the transformer in the end of an interval dt.

From expression (7) it is possible to define Θ:

,                                          (8)

simultaneously

.                                               (9)

From the formula (9) quantity can be in advance discovered

,                                              (10)

for each device of the transformer on observational or design values of losses ΔÐn and the erected temperature Θn. Quantity α · S is invariable for each device of a construction of the transformer.

On the basis of expression (9) taking into account (8) and (10) it is possible to calculate power losses for each device of a construction in time dt:

.

Active power net losses in the transformer in time dt develop of losses in each n-th device of the transformer:

.

Losses of electrical energy in time dt:

.

Summation of losses for each space of time gives common losses in the transformer for required space of time at any load pattern.

Deductions.

1. The essence of an offered expedient of definition of losses of the active electric power consists in a tank transformer that the transformer and surrounding medium temperature and in measuring space of times equal on two, three orders less than a thermal time constant is measured, the gain of temperature of the transformer is calculated, the difference between temperature of the transformer and a surrounding medium is spotted and losses of the active electric power in the transformer are calculated under the formula (5).

2. The essence of an offered expedient of definition of losses of the active electric power consists in the air transformer that the temperature of magnetic system is measured, a winding and a surrounding medium and in measuring space of times equal on two, three orders less than a thermal time constant of the transformer, are calculated gains of temperatures of magnetic system and a winding, differences between temperatures of magnetic medium, a winding and a surrounding medium are spotted. Losses of the active electric power in the transformer are calculated under the formula (6).

3. At a non-uniform load pattern it is expedient to calculate electric power losses in each device of a construction of the transformer separately taking into account the rated erected temperature for each condition of a fill of the transformer and invariable design data of its devices. Such solution considers losses in windings, in magnetic system, from current and voltage upper harmonics, from asymmetry of a loading.

4. The formula (5 and 6) allow to consider all losses of the active electric power oozed in the transformer in the form of heat. Medial meaning of quantity of an error of evaluation under the formula (6) during experiment has made 9,3 %.

 

The literature:

1. Petrov G.N. Electric machine. In 3 parts. Part 1. Introduction. Transformers. The textbook for high schools. Ì.: Energy, 1974. 240 pages.

2. The patent. 2380715 Russian Federations, ÌPÊ G 01 R 19/02, G 01 R 11/00. The counter of losses of the electric power / V.F. Ermakov, E.S. Balykin, E.V. Ermakova, I.V. Zajtseva, J.M. Reshetnikov; V.F. Ermakov. ¹ 2008128966/28; announcement 15.07.2008; it is published 27.01.2010.